8 Settings
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
90
8.16 Constant cos phi
Overview
With this function you can set a constant cos phi (cos φ).
This function should be set only when requested by country regulations, authorities or your grid operator.
Accessing the menu
Main menu > Active/Reactive Pwr > Reactive Power Ctrl > Constant cos phi
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
Inverter Info.
General Settings
2. Use the buttons and to select Active/Reactive Pwr.
To conrm your selection, press the button
ENT
.
energy production
Adj. would effect
3. The menu is protected by password 5555. Use the buttons and to set each digit.
To conrm a digit, press the button
ENT
.
Reactive Power Ctrl
Active Power Ctrl
4. Use the buttons and to select Reactive Power Ctrl. The current setting is
displayed behind the menu entry.
5. Use the buttons and to select Constant cos phi. The current setting is dis-
played behind the menu entry.
Cos phi: Ind 1.00
Mode: ON
6. To change the mode, use the buttons and to select Mode and press the button
ENT
.
To switch the function on, select ON and press the button
ENT
.
To switch the function off, select OFF and press the button
ENT
. When you switch the
function off, you can ignore the following steps.
Do not change this setting without prior
consultation with Delta Solar Support.