Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
8 Settings
Cos phi: Ind 1.00
Mode: ON
7. If you need to change the cos phi (cos φ), use the buttons and to select Cos
phi and press the button
ENT
.
8. To change the parameter value, use the buttons and .
To conrm your setting, press the button
ENT
.
To cancel the action, press the button
ESC
.
Congurable Parameters
Parameter Description Value range
Mode
Switches the function on and off.
ON | OFF
Default value: OFF
Cos phi
Sets up a cos phi so that the inverter can feed reactive power into the
grid.
ind 0.8 ... cap 0.8
Do not change this setting without prior
consultation with Delta Solar Support.