Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
6 Installation
6.9 Connecting to the solar modules (DC)
Read chapter “5. Planning the installation”,
p. 19 before you start installation.
DANGER
Risk of death or serious injury from electro-
cution
Potentially fatal voltage may be applied to the
DC connections of the inverter. When light is fall-
ing on solar modules, they immediately start pro-
ducing energy. They do so, even when the sun is
not shining directly onto the solar modules.
Never disconnect the solar modules when the
inverter is powered.
First switch off the grid connection so that the
inverter cannot feed energy into the grid.
Turn the AC/DC Disconnection switch to
position OFF.
Make sure the DC connections cannot be
accidentally touched.
NOTICE
Improperly sized PV array.
An improperly sized PV array can cause damage
to the inverter.
Consider the technical specications of the
inverter (input voltage range, maximum cur-
rents and maximum input power, see “13.
Technical data”, p. 113) when planning the
size of the PV array.
NOTICE
Penetrating humidity.
Humidity can penetrate through unused DC con-
nectors into the inverter.
To ensure protection degree IP65, protect all
unused DC connectors with the caps deliv-
ered with the inverter.
NOTICE
Machine and equipment damage may occur.
Exceeding the maximum current per DC input
can cause an overheating of the DC inputs.
Always consider the maximum current of the
DC inputs when planning the installation.
Cable colors
Use a red cable for DC+ and a black cable for DC–.
Connector types
The DC plugs are delivered with the inverter. The plugs can also
be ordered from Multi-Contact at www.multi-contact.de. The
required size depends on the wire cross-section and thickness of
the cable used.
DC connector type on the
inverter
Counterpiece required for
the cable
The DC-MINUS connector is a
male socket.
A female plug is required for
the black DC cable.
The DC-PLUS connector is a
male socket.
A male plug is required for the
red DC cable.
You can download the manual from the Multi-Contact website.
This manual will also tell you which tools are required.
France: Safety caps are needed for each
DC input that is connected to a string of
solar modules.
It is recommended to use a special open-
end spanner for the MC4 DC connectors
if you need to disconnect MC4 DC con-
nectors from the inverter. Otherwise you
might destroy the DC Connectors.

Table of Contents

Other manuals for Delta RPI M6A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M6A and is the answer not in the manual?

Delta RPI M6A Specifications

General IconGeneral
BrandDelta
ModelRPI M6A
CategoryInverter
LanguageEnglish

Related product manuals