8 Settings
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
70
8.6 Inverter ID
Overview
With this function you can set an ID for the inverter. The inverter ID is used to identify the inverter in a RS485 connection. The inverter
ID is also used in monitoring systems.
► Set a different inverter ID for each inverter in the PV plant. Otherwise, the inverters cannot be correctly identied.
► On the last inverter in the RS485 connection, switch on the RS485 termination resistor. For a description, see
“6.6 Connecting communication port I”, p. 58.
Accessing the menu
Main menu > Install Settings > Inverter ID
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
Inverter Info.
General Settings
2. Use the buttons and to select Install Settings.
To conrm your selection, press the button
ENT
.
energy production
Adj. would effect
3. The menu is protected by password 5555. Use the buttons and to set each digit.
To conrm a digit, press the button
ENT
.
4. Use the buttons and to select Inverter ID. The currently set inverter ID is
displayed behind the menu entry.
To conrm your selection, press the button
ENT
.
5. Use the buttons and to set the inverter ID.
To conrm your setting, press the button
ENT
.
Congurable Parameters
Parameter Description Value range
Setting ID
Sets the inverter ID that is needed to identify the inverter when a PV
plant contains multiple inverters.
001 ... 254