8 Settings
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
84
8.13 Power limitation
Overview
Values have been set based upon country standards. If you modify these values, you will lose certication. Therefore
you should set this function only when requested by country regulations, authorities or your grid operator.
With this function you can limit the active power fed into the grid.
The power limitation set with this function relates to the value set for the Max. Power parameter in the installation settings. For a
description of the Max. Power parameter, see “8.12 Max. Power (Maximum feed-in power)”, p. 83.
Example
You have set the maximum power to 80%.
If you additionally set a power limitation of 70%, the total maximum active power is calculated as
50 kW x 80% x 70% = 28 kW.
Accessing the menu
Main menu > Active/Reactive Pwr > Active Power Ctrl > Power limit
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
Inverter Info.
General Settings
2. Use the buttons and to select Active/Reactive Pwr.
To conrm your selection, press the button
ENT
.
energy production
Adj. would effect
3. The menu is protected by password 5555. Use the buttons and to set each digit.
To conrm a digit, press the button
ENT
.
Active Power Ctrl
4. Use the buttons and to select Active Power Ctrl.
To conrm your selection, press the button
ENT
.
Power vs. Frequency
Power Limit
5. Use the buttons and to select Power Limit.
To conrm your selection, press the button
ENT
.
Do not change this setting without prior
consultation with Delta Solar Support.