6. To change the mode, use the buttons and to select Mode and press the button
ENT
.
To switch the function on, select ON and press the button
ENT
.
To switch the function off, select OFF and press the button
ENT
. When you switch the
function off, you can ignore the following steps.
7. If you need to change a parameter, use the buttons and to select the parameter
and press the button
ENT
.
8. To change the parameter value, use the buttons and .
To conrm your setting, press the button
ENT
.
To cancel the action, press the button
ESC
.
9. Repeat steps 7 to 8 for other parameters if you need to change them.
Congurable Parameters
Parameter Description Value range
Mode
Switches the function on and off.
ON | OFF
Default value: OFF
Q upper
Sets up the upper limit for the reactive power which is set as a cos
phi (cos φ).
ind 0.8 .. cap 0.8
P upper
Sets up the upper limit for the active power which is set in per cent of
the nominal power.
0 .. 100%
Q lower
Sets up the lower limit for the reactive power which is set as a cos phi
(cos φ).
ind 0.8 .. cap 0.8
P lower
Sets up the lower limit for the active power which is set in per cent of
the nominal power.
0 .. 100%
V lock-in
The lower limit of the grid voltage range in which the function is
active. The parameter is used for Italy only.
230.0 .. 253.0 V
V lock-out
The upper limit of the grid voltage range in which the function is
active. The parameter is used for Italy only.
207.0 .. 230.0 V
Do not change this setting without prior
consultation with Delta Solar Support.