NetworX Version 3 Installation Manual
14
Standard onboard outputs NX-xx(-GSM)-EUR NX-xx(-GSM)-LB-EUR
Built-in Siren Driver (BELL+, BELL-)
Electronic output, rating: 1 A at 13.8 V ± 10%
High current outputs (RLY1 and RLY2)
Relay, rating: 1 A at 13.8 V ± 10%
Control panel fuses NX-xx(-GSM)-EUR NX-xx(-GSM)-LB-EUR
Battery
5 A, resettable
AUX PWR+
1 A, resettable
POS
1 A, resettable
Mains, mains fuse [4]
315 mA, T 250V 20x5 630 mA, T 250V 20x5
Environmental NX-xx(-GSM)-EUR NX-xx(-GSM)-LB-EUR
Operating temperature
−10 to +55°C
Humidity
Max 95% non condensing
IP protection grade
IP30
Colour
Beige
Dimensions
220 x 253 x 112 mm 394 x 256 x 118 mm
Shipping weight
1.8 kg 2.8 kg
EN 50131 grade and class
Securuty Grade 2, Environmental Class II
General features NX-xx(-GSM)-EUR NX-xx(-GSM)-LB-EUR
Code combinations [6]
From 10,000 (4 digits) to 1 million (6 digits)
End-of-line resistor
3.3 kΩ
Data retention (log, program settings)
20 years
[1] Current available for AUX PWR+, POS and battery charge outputs (non-EN-mode).
[2] Maximum permanent current to power devices external to the control equipment in the absence of alarm
conditions (EN-mode).
[3] Max ripple voltage only when empty battery is charging.
[4] Mains fuse is a part of the mains terminal block.
[5] Minimum voltage only when mains supply voltage is disconnected and system is running on battery.
[6] There are no disallowed codes.
[7] Optional function for the EN 50131 compliance.
WARNING: Before removing the mains fuse, mains power must be disconnected.
Auxiliary current and battery capacity
Table 3. NX-xx(-GSM)-EUR maximal available auxiliary current
Battery 7.2 Ah
Discharge
Time (h)
Charge
Time (h)
Auxiliary current (mA)
12 72 350 EN 1&2