EasyManuals Logo
Home>Honeywell>Security System>Galaxy Flex V3 Series

Honeywell Galaxy Flex V3 Series User Manual

Honeywell Galaxy Flex V3 Series
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Wire detectors to zones Galaxy Flex Installer Manual
18
1. Terminate any unused zones inputs with a 1 k resistor and program them as SPARE
(Menu 52.1.x.1=18).
2. If required, reprogram zone configurations and the resistance preset values using the
Zone Resistance menu (51 ent 46 ent).
3. If required, customise each zone to a specific preset using the Resistance Select menu
(52 ent 9 ent).
4. Limit the cable run on each zone to no more than 500 m. For presets 11 and 12, limit
the cable run to no more than 100 m.
Detector connection
Wire detectors to zone terminals according to the following diagram:
Additional zone configuration information
Zones can be programmed with different resistance ranges or for normally-closed (N/C)
loops for zone status activation (see Zone Resistance [51.46] and Appendix H).
If a detector has separate fault and mask indications use the wiring shown in Figure 4.
Figure 4 Option 12 - Double balanced 1k fault/mask monitoring wiring
When this wiring mode is used, ensure only one detector is set to report fault conditions, and
l
imit the number of detectors or contacts of any type to a maximum of 2.
Note: The recommended maximum cable run from a zone to a detector is 500 metres in all
other configurations.
In end-of-line mode use the wiring shown in Figure 5.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Flex V3 Series and is the answer not in the manual?

Honeywell Galaxy Flex V3 Series Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy Flex V3 Series
CategorySecurity System
LanguageEnglish

Related product manuals