ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 10 997-291, Version 3.05
November 2010
4.1.4.3 Device Selection
All modules that are required to activate a Non-
fire Control Matrix entry must be configured as
type AUX.
The Immediate release switch should be type
MCP or MON.
All modules of type CTRL must be set to non-
silenceable so that the panel’s SILENCE/
RESOUND pushbutton does not control the
extinguishant release. Set their open-circuit
supervision OFF.
4.1.4.4 HOLD Options
The HOLD switch may have one of four effects
on the delay timer. Each effect has a three-
character name:
AHJ - When HOLD is deactivated, the timer
starts again from its configured value.
To configure this mode:
1 Set non-fire to ‘HOLD mode: RE-START or
Extend Timer’.
2 Leave activation delay at the panel’s default
value (60 seconds).
Control Modules used to
activate the direction valve
and the release valve
MUST be configured as
NON-SILENCEABLE.