ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 11 997-291, Version 3.05
November 2010
NYC - When HOLD is deactivated, the timer
starts again from a length of time longer than
its configured value.
To configure this mode:
1 Set non-fire to ‘HOLD mode: RE-START or
Extend Timer’.
2 Set activation delay to a period longer than
the panel’s default value of 60 seconds.
ULI - When HOLD is activated, the timer is
paused at a configured number of seconds
before release. When HOLD is deactivated the
timer restarts from this pause time.
To configure this mode:
1 Set non-fire to ‘HOLD mode: Run timer then
PAUSE’.
2 Ensure the Alarm entries are ‘Auto Release’
or ‘Manual Release’ without ‘Over-ride
HOLD’.
IRI - As ULI but HOLD switch activity is ignored
if two or more zones are in co-incident alarm.
To configure this mode:
1 Set non-fire to ‘HOLD mode: Run timer then
PAUSE’.
2 Ensure the Alarm entries are ‘Auto Release’
or ‘Manual Release’ with ‘Over-ride HOLD’.
3 Ensure Alarm entries have the ‘Multiple Zone
Coincidence’ option selected.