Updating the firmware 82
b.
Press the Reset button on either the Display Unit or the Core Unit.
On the terminal emulation session screen running on the host computer, the POST executes, and
the following prompt appears:
Press any key in 5 seconds to enter the Service menu.
c. Press a key to enter the HP Intelligent PDU Service Menu (on page 64).
d. On the Service Menu, enter 2 at the prompt to select PDU LED Pass-through.
e. Enter 3 at the prompt to exit the Service Menu.
f. After the > prompt appears, close the terminal emulation program.
3. Launch the HP Power Device Flash Utility.
4. Select Serial as the transfer mode.
5. Select Image.bin as the file type.
6. Click the Browse button (...) to navigate to a saved image.bin file.
7. Select the COM port of the host computer.
8. Click Flash.
FTP Flash Mode
To update the firmware for a single iPDU:
1. Be sure that the iPDU is connected to the network.
2. Note the IP address of the iPDU.
3. Launch the HP Power Device Flash Utility.
4. Select FTP as the transfer mode.
5. Select Image.bin as the file type to flash the firmware.
6. Click the Browse button (...) to navigate to a saved image.bin file.
7. Enter the iPDU IP address, then click >> to add the IP address to the table.
To remove IP addresses from the table, highlight the unwanted IP addresses, and then click X.
8. Click Ping to verify that the IP address is valid. If a good connection is detected, the Flash button
enables
9. Enter your username and password.
10. Click Flash.
To update the firmware for multiple iPDUs:
1. Be sure that all iPDUs are connected to the network.
2. Note the IP address of each iPDU.
3. Launch the HP Power Device Flash Utility.
4. Select FTP as the transfer mode.
5. Select Image.bin as the file type to flash the firmware.
6. Click the Browse button (...) to navigate to a saved image.bin file.
7. Enter the IP address for each iPDU. Click >> to add each IP address to the table.
To remove IP addresses from the table, highlight the unwanted IP addresses, and then click X.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP Intelligent Power Distribution Unit and is the answer not in the manual?

HP Intelligent Power Distribution Unit Specifications

General IconGeneral
BrandHP
ModelIntelligent Power Distribution Unit
CategoryPortable Generator
LanguageEnglish

Related product manuals