Communication sequence
The communication sequence is as follows
External
controller
Inverter
Frame 1
Frame 2
Wait time
Frame Start: Frame start is recognized by signal line data transmitted
Frame Complete: Frame completion is recognized by no data during 4, 5-character time.
Frame 1: Transmit from external controller to VFD.
Frame 2: Indication reflects from VFD to external controller
3.7.4 Communication Frame Type and Form
External Controller Transmit Frame
Inverter
Communication
number
1
st
byte : Group
2
nd
byte : Index
(Note1)
1
st
byte : 0x00
2
nd
byte : N(0x01~0x08)
Inverter response frame
Inverter
Communication
number
Request parameter number x 2
*Frame Size = 5 + Request parameter number x 2