N700E INSTRUCTION MANUAL
3-6
3.1.4 Expanded Function Mode of b Group
Code
Name
Edit
Range
Unit
Res
Default
Restart Mode
b01
Restart Select
X
0: No Restart
1: Restart from 0Hz
2: Resume at frequency
corresponding motor speed
3: Resume at motor speed; then,
decelerated to stop
-
-
0
b02
Line Loss Ride-Through Time
X
0.3 to 1.0
Sec
0.1
1.0
b03
Line Loss Ride-Through Run
Delay
X
0.3 to 10.0
Sec
0.1
1.0
Electronic Thermal Overload Fault Setting
b04
Motor Thermal Overload Level
X
20.0 to 120.0
%
0.1
100.0
b05
Motor Thermal Overload Profile
X
0: Self Cooling
1: Forced Cooling
0
b06
Overload/Overvoltage
Restriction Mode
X
0: OLR = OFF, OVR = OFF
1: OLR = ON, OVR = OFF
2: OLR = OFF, OVR = ON
3: OLR = ON, OVR = ON
-
-
3
b07
Overload Restriction Level
X
20.0 to 200.0
%
0.1
HD : 180%
ND : 150%
(≤200HP)
HD : 150%
ND : 120%
(≥250HP
,300LF~
750LF)
b08
Overload Restriction
Deceleration Rate
X
0.1 to 10.0
Sec
0.1
1.0
Software Lock Mode
b09
Software Lock Mode
X
0: All Parameters are locked except
b09 when SFT terminal input
is ON
1: All parameters are locked
except b09 and F01
by SFT terminal signal
2: All parameters are locked
except b09
3: All parameters are locked
except b09 and F01
4: All parameters are locked
except b09, F01, F02, and F03
-
-
0