EasyManuals Logo

Hyundai N700E User Manual

Hyundai N700E
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
N700E INSTRUCTION MANUAL
3-17
3.3 F Group Parameters
F group holds very basic frequency related parameter values to operate the N700E VFD.
F01 Output Frequency Setpoint
Range: 0.00 ~ 400.00 Hz in 0.01 Hz
Range: 0.00 ~ 300.00 Hz in 0.01 Hz for Sensor-less Vector Control (A31=2)
This parameter displays the frequency setpoint for the VFD.
VFD Frequency can be controlled by various sources set in A01.
If A01=0: Use the Volume Key on the panel
If A01=1: Use the Terminal (O-L, OI-L)
If A01=2: Use Up/Down Keys
If A01=3: Use Control Terminal Input (RJ45)
(Except 300LF~750LF)
If A01=4: Use Control Terminal Input,(RXP-RXN)
if A01=5: Fieldbus (option)
Related Parameters: A01
F02 Acceleration Time 1
Range: 0.1 ~ 999.9 Sec in 0.1 Sec
1000 ~ 3000 Sec in 1 Sec
Acceleration time from 0Hz to Maximum Frequency (A04)
Related Parameters: A54, A56, A57,A59
F03 Deceleration Time 1
Range: 0.1 ~ 999.9 Sec in 0.1 Sec
1000 ~ 3000 Sec in 1 Sec
Deceleration time from Maximum Frequency (A04) to 0Hz
Related Parameters: A55, A56, A58, A60
F04 Rotation Direction
0: Forward Run
1: Reverse Run
Sets the direction of VFD to forward or reverse at keypad operation only
Related Parameters: A02
100 %
V
Base
Frequency
A03
F
Max
Frequency
A04

Table of Contents