6 8
KEB COMBIVERT F4-C
6
Name: Basis
29.01.98
Functional Description Parameter Sets
© KEB Antriebstechnik, 1997
All Rights reserved
Chapter Section Page
Date
Input-coded set selection
ID IB I4 I2 I1 Set
000000
000011
000202
003003
040004
500005
503003
503011
Picture 6.8.3.c Input-coded parameter set selection
At input-coded set selection
- maximal 7 of the internal or external inputs may be programmed for set selection
(0…7 sets) within one parameter set to avoid set selection errors.
- the lowest of the selected inputs has priority
(I1 > I2 > I3 > I4 > IA > IB > IC > ID)
Eample1: With 5 inputs (I1, I2, I4, IB and ID) set 0…5 shall be selected
1.) Adjust parameter di.3, di.4, di.6, di.8 and di.10 to value „1“
2.) Parameter di.5, di.7 and di.9 must be set to 1
3.) Adjust Fr.2 to vlaue „3“ (set selection input-coded via terminal strip)
Set 0
Set 1
Set 2
Set 3
Set 4
Set 5
I1
I2
I4
IB
ID
6.8.4 Locking of Para-
meter Sets
Parameter sets that shall not or may not be selected can be locked with Fr.3. If the
locked set is selected, the inverter switches off with set selection error (E.SEt).
Value Locked set Example
10 -
21 -
42 4
83 -
16 4 -
32 5 32
64 6 -
128 7 -
Set 2 and set 5 locked Sum 36
Fr.3 Parameter set lock

Table of Contents

Other manuals for KEB COMBIVERT F4-C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F4-C and is the answer not in the manual?

KEB COMBIVERT F4-C Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F4-C
CategoryDC Drives
LanguageEnglish

Related product manuals