4.3.1 Operation in
CP-Mode
4.3 CP-Parameter
The Customer-Parameters (CP) are a special group of parameter. With the
exception of CP.0 (Password input), they can be defined by the user. The following
Parameters are preset at delivery.
Advantages from it: - operator-friendly for the customer
- critical parameters are protected against maloperation
- low documentation cost for the machine builder
FUNCT
SPEED
▲
START
▼
STOP
▲
START
▼
STOP
Adjustment of
parameter number
Adjustment of
parameter value
Compared to the Application-Mode the operation in the CP-Mode is easier because
parameter set selection and parameter group selection are unnecessary.
The following list shows the CP-parameter group predefined by us. The definition
of the CP-parameters is done in the User-Definition-Parameters (ud). How you can
define your own parameters is described in Chapter 5.
Display Parameter Setting Range Resolution Factory Setting Source
CP. 0 Password input 0...9999 1 - ud. 0
CP. 1 Actual frequency display - 0,1 Hz - ru. 3
CP. 2 Status display - - - ru. 0
CP. 3 Actual load - 1 % - ru. 7
CP. 4 Peak load - 1 % - ru. 8
CP. 5 Rated frequency 0...409,58 Hz 0,0125 Hz 50,0 Hz 0.uF. 0.
CP. 6 Boost 0...25,5 % 0,1 % 2 % 0.uF. 1.
CP. 7 Acceleration time 0,01...300 s 0,01 s 10 s 0.oP.11.
CP. 8 Deceleration time 0,01...300 s 0,01 s 10 s 0.oP.12.
CP. 9 Minimum frequency 0...409,58 Hz 0,0125 Hz 0 Hz 0.oP. 4
CP.10 Maximum frequency 0...409,58 Hz 0,0125 Hz 70 Hz 0.oP. 5.
CP.11 Fixed frequency 1 0...409,58 Hz 0,0125 Hz 5 Hz 0.oP.22.
CP.12 Fixed frequency 2 0...409,58 Hz 0,0125 Hz 50 Hz 0.oP.23.
CP.13 Fixed frequency 3 0...409,58 Hz 0,0125 Hz 70 Hz 0.oP.24.
CP.14 max. ramp current 10...200 % 1 % 140% 0.Pn. 5.
CP.15 max. constant current 10...200 % 1 % 200% 0.Pn.13.
CP.16 Speed search 0...15 1 8 0.Pn. 7.
CP.17 Voltage stabilization 150...649 V,oFF 1 V off 0.uF. 8.
CP.18 Slip compensation -2,50...2,50 0,01 0=off 0.cn. 1.
CP.19 Autoboost -2,50...2,50 0,01 0=off 0.cn. 2.
CP.20 DC-braking 0...9 1 7 0.Pn. 8.
CP.21 DC-braking time 0...100 s 0,01 s 10 s 0.Pn.11.
CP.22 Relay output 0...25 1 2 0.do.2.
CP.23 Frequency level 0...409,58 Hz 0,0125 Hz 4 Hz 0.LE. 2.
CP.24 Setpoint signal 0...2 1 0 An. 6.
4.3.2 Factory Setting