6 1
Name: Basis
KEB COMBIVERT F4-C
16
09.04.99
© KEB Antriebstechnik, 1999
All Rights reserved
Functional Description
Chapter Section Page
Date
Operating and Appliance Displays
Adr.
min max
default
Adr.
min max
default
2C01h
0,1
A
LTK
4600
6.1.5 Description of In-Parameters
2C00h
In. 0 Inverter type
1
hex
-
--
The inverter type is indicated in hexadecimal numbers. The bits have following meaning:
bit 0: Voltage class 0 = 200V
1 = 400V
bit 1-5 Unit size 05,07,09,....
bit 6-9 Control type 0 = 0A.F4 ( F4-C / up to housing size E )
1 = 0B.F4 ( F4-S / up to housing size E )
2 = 00.F4 ( F4-C / from housing size G upwards)
bit 10-12 Rated operating frequency 0 = 2kHz
1 = 4kHz
2 = 6kHz
3 = 8kHz
4 = 10kHz
5 = 12kHz
6 = 14kHz
7 = 16kHz
bit 13-15 Maximal operating frequency 0 = 2kHz
1 = 4kHz
2 = 6kHz
3 = 8kHz
4 = 10kHz
5 = 12kHz
6 = 14kHz
7 = 16kHz
Example:
hex F C 9 D
binary 1 1 1 1 1 1 0 0 1 0 0 1 1 1 0 1
decimal 7 7 2 14 1
=> 14.F4.C 16 / 16kHz 400V
In. 1 Rated inverter current
Display of rated inverter current in A. The value is determined from the power circuit identification (LTK) and cannot be
changed.