15
ANTRIEBSTECHNIK
6
115
09.04.99
KEB COMBIVERT F4-C
Name: Basis
6
© KEB Antriebstechnik, 1999
All Rights reserved
Functional Description
Chapter
Section
Page
Date
Operating and Appliance Displays
Adr.
min max
default
Adr.
min max
default
Adr.
min max
default
ud.11
!ud.11!
ud.11
!ud.11!
202Dh
ru.45 Display analog option
0,1
%
-
100-100
This parameter displays the percentual value of the signal at the optional analog input.
-10V...0...+10V = -100%...0...100%
202Eh
ru.46 Ramp output frequency
0,0125
Hz
-
409,58-409,58
This parameter displays the frequency at the output of the ramp generator. If the internal PI-controller is not active, the
displayed frequency corresponds to the output frequency ru.3.
202Fh
ru.47 Actual frequency encoder
0,0125
Hz
-
409,58-409,58
The displayed value depends on cn.3.
cn.3 = 0 (default) The actual frequency of ru.3 is displayed.
cn.3 = 1 or 2 The current actual frequency of the encoder interface (option) is displayed. This measured value
corresponds to the real slip-afflicted actual speed.
1: channel 1
2: channel 2
A counter-clockwise rotating field (reverse) is represented by a negative sign. Precondition is the correct phase connection
of the motor.
For a closed-loop-controlled system it is imperative to ensure the correct correct phase connection, otherwise
the controllers would run into their limit.

Table of Contents

Other manuals for KEB COMBIVERT F4-C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F4-C and is the answer not in the manual?

KEB COMBIVERT F4-C Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F4-C
CategoryDC Drives
LanguageEnglish

Related product manuals