Functional Description Special Functions
Param. Adr.
min
max
default
ENTER
PROG.
R/W
Step
Counter/Level 1...4
(LE.41...LE.44)
The conditions, at which the counter is reset, may be selected from the following
table. The conditions are OR-linked, i.e. if one of the adjusted conditions is met the
counter (see ru.33) is reset. If LE.45 and LE.46 are active at the same time the
counter remains on 0s.
Bit Value Counting Condition
0 1 Input ST (X1.19)
1 2 Input RST (X1.20)
2 4 Input F (X1.10)
3 8 Input R (X1.11)
4 16 Input I1 (X1.4)
5 32 Input I2 (X1.5)
6 64 Input I3 (X1.6)
7 128 Input I4 (X1.7)
8 256 Modulation active
9 512 Modulation inactive
10 1024 Actual frequency = Set frequency
11 2048 Active set changes
12 4096 Power On Reset
Counter/Reset Condition
(LE.45)
LE.41...LE.44 defines the level for the switching condition 25 („Timer > Level“). If the
counter exceeds an adjusted level, the switching condition is set.
Used Parameters
ru.33 2021h - - - 0 327,67 0,01 0 s / h depending on LE.47
LE.35 2B23h ✔✔- 0,00 100 s 0,01s 0,00 0=off
LE.41 2B29h ✔✔- 0,00 300,00 0,01 0 s / h depending on LE.47
LE.42 2B2Ah ✔✔- 0,00 300,00 0,01 0 s / h depending on LE.47
LE.43 2B2Bh ✔✔- 0,00 300,00 0,01 0 s / h depending on LE.47
LE.44 2B2Ch ✔✔ - 0,00 300,00 0,01 0 s / h depending on LE.47
LE.45 2B2Dh ✔ - - 0 4096 1 0 -
LE.46 2B2Eh ✔ - - 0 1024 1 0 -
LE.47 2B2Fh ✔ - - 0 1 1 0 0 = s / 1 = h
In ru.33 the current counter content is indicated in seconds or hours (depending on
LE.47). By writing on ru.33 the counter can be set to 0. If the resolution in LE.47 is
changed during the running time, the counter content is kept, but it is now interpreted
according to the new resolution.
Current Counter Content
(ru.33)