Configuration
7-256

SHB9300CRV EN 2.0
7.7.3.8 External fault EEr
Purpose
Monitores the process.
MONIT
DCTRL-TRIP
MONIT-EEr
C0884/3
C0871
Fig. 7-201 External fault EEr
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DCTRL-TRIP d C0884/3 bin C0871 2 54 -
MONIT-EEr d - - - - - -
Function
The signal EEr is generated from the signal DCTRL-TRIP-SET at the input (level evaluation). With
factory setting, this signal is generated from the terminal X5/E4. Here you can connect an external
encoder which can control the reaction required of the controller.
It is however also possible to use any other binary signal source.
Features:
l
LECOM No.: 91, 1091, 2091
l
Reaction: TRIP, MESSAGE, WARNING or OFF