Configuration
7-272

SHB9300CRV EN 2.0
7.7.4 Fault indication via digital output
Inthefunctionblock DIGOUTthe fault messages TRIP, messageand warning canbeassigned to the
digital outputs (e. g. terminals X5/A1¡ X5/A4).
Display TRIP or Message or Warning individually (individual indication):
1. Select digital output in the code level under C0117 and subcode.
2. Assign TRIP or Message or Warning in the parameter level.
Display TRIP, Message, Warning collectively (collective indication):
1. Assign TRIP, message and warning to an OR-element.
2. Select digital output in the code level under C0117 and subcode.
3. Assign output of the OR-element in the parameter level.
Display monitoring functions individually:
1. Select digital output in the code level under C0117 and subcode.
2. Assign monitoring function (e.g. MONIT-OH7).