6.3 Engineering port
Parameter
Address Name / seng range / [default seng] Informaon
0x2450 Engineering port control Acvaon of the engineering port sengs (Ethernet).
0 No acon/No error
1 Restart with current values
10 Busy
11 Acon cancelled
12 Faulted
0x2451:001 Engineering port sengs: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Seng of the IP address.
The default seng 1661315264 corresponds to the following values:
1661315264
0x6305A8C0
0xC0.0xA8.0x05.0x63
192.168.5.99
0x2451:002 Engineering port sengs: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Seng of the subnet mask.
The default seng 16777215 corresponds to the following values:
16777215
0xFFFFFF
0xFF.0xFF.0xFF.0x00
255.255.255.0
0x2451:003 Engineering port sengs: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Seng of the gateway address.
0x2451:004 Engineering port sengs: DHCP Use (enable) of the Dynamic Host Conguraon Protocol (DHCP).
0 Disabled
1 Enabled
6.4 Name server addresses
Two corresponding name servers can be entered via IP address for name resoluon if network
funcons are used.
For safety reasons, the Ethernet access must not be connected directly to the
Internet. The specied Domain Name Server must be in the local network or
available from the local network.
Please observe the rewall sengs of the network.
Parameter
Address Name / seng range / [default seng] Informaon
0x2459:001 Name server addresses: Name server address 1
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Specicaon of an IP address for a Domain Name Server (DNS).
As a funcon of the DHCP seng, the seng of the name server
address only becomes eecve when the device is restarted.
0x2459:002 Name server addresses: Name server address 2
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Device sengs
Engineering port
26

Table of Contents

Other manuals for Lenze C 750

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze C 750 and is the answer not in the manual?

Lenze C 750 Specifications

General IconGeneral
BrandLenze
ModelC 750
CategoryController
LanguageEnglish

Related product manuals