11.3 Diagnosc parameters
11.3.1 PLC diagnoscs
The following informaon may be retrieved for diagnosc purposes:
•
Informaon on the event currently acve in the controller (event monitor)
•
Status of the SD card
•
Available applicaon credit / required applicaon credit
•
Dual use license
•
Temperature of the control card and CPU
•
Status of the applicaon
Parameter
Address Name / seng range / [default seng] Informaon
0x2010:001 Device event monitor: EreignisortEvent locaon
•
Read only
Display of informaon on the event currently pending in the controller.
0 No error
1 Funconal safety
4 Basic sengs
5 Communicaon
6 Kinemacs
7 Moon
8 Technology applicaon
0x2010:002 Device event monitor: Event type
•
Read only
0 No response
1 Fault > CiA402
2 Warning
11 Informaon
13 Warning locked
15 Trouble > logbook only
16 Trouble
18 Fault > logbook only
19 Fault > Applicaon quick stop > Quick stop
20 Fault > inverter quick stop > quick stop
21 Fault > inverter quick stop > inverter
disabled
23 Fault
0x2010:003 Device event monitor: Event status
•
Read only
0 No event acve
1 Reset possible
2 Reset not possible
0x2010:005 Device event monitor: Number of current event
•
Read only
0x2010:006 Device event monitor: Time stamp of current event
•
Read only: x ns
0x2012:001 Device informaon: SD card status
•
Read only
Display whether an SD card is inserted.
0 No SD card connected
1 SD card connected
0x2012:002 Device informaon: Applicaon Credit available
•
Read only
Display of the applicaon credit available on the SD card
0x2012:003 Device informaon: Dual use licence
•
Read only
Display whether a dual-use license is available.
0 Not available
1 Available
0x2012:004 Device informaon: SD card total memory
•
Read only
Display of the total memory capacity of the SD card in kilobytes.
Diagnoscs and fault eliminaon
Diagnosc parameters
PLC diagnoscs
95