8.1.1 EtherCAT state machine
Before communicaon via EtherCAT is possible, the eldbus scans the EtherCAT state machine
when boong. The following illustraon shows the possible state change from the point of
view of an EtherCAT slave:
Safe-Operational
Bootstrap
Operational
Pre-Operational
Init
Fig. 1: EtherCAT state machine
State Descripon
Init
Inializaon phase
No SDO/PDO communicaon with the slaves
Device can be detected by eldbus scan
Pre-operaonal
The eldbus is acve.
SDO communicaon (mailbox communicaon) is possible.
No PDO communicaon
Safe-operaonal
SDO communicaon (mailbox communicaon) is possible.
PDO communicaon:
The input data in the process image is updated.
The output data from the process image is not transferred to the slaves.
Operaonal Normal operaon
SDO communicaon
PDO communicaon
Fieldbus synchronizaon has been successful (if used)
A eldbus scan is possible in any EtherCAT state.
The SDO communicaon via the EtherCAT bus is only possible if at least the
"Pre-Operaonal" state has been reached.
Conguring the network
EtherCAT
EtherCAT state machine
38

Table of Contents

Other manuals for Lenze C 750

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze C 750 and is the answer not in the manual?

Lenze C 750 Specifications

General IconGeneral
BrandLenze
ModelC 750
CategoryController
LanguageEnglish

Related product manuals