eration 1
I1 2nd point 238 I33 Empty ——
I2 3rd point 239
I3 4th point 240
I4 5th point 241
I34
UNIT VERIFY ERR.
FUSE BREAK OFF
SP. UNIT ERROR
2
I5 6th point 242
I6 7th point 243
I7 8th point 244
I8 9th point 245
I35
OPERATION ERROR
SFCP OPE. ERROR
SFCP ECE. ERROR
EX. POWER OFF
3
I9 10th point 246
I10 11th point 247
I36
ICM. OPE ERROR
FILE OPE. ERROR
4
I11 12th point 248 I37 Empty ——
I12 13th point 249 I38 PRG. TIME OVER 5
I13 14th point 250
I14 15th point 251
I39
Error factor
4
CHK instruction execution
Anunciator detection
6
I15
QI60/A1SI61
interrupt module
factor
16th point 252
I16 1st point 224
I17 2nd point 225
I40 to
I48
—— Empty ——
I18 3rd point 226 I49 Internal timer factor 0, 2 to 1.0mg
5
7
I19 4th point 227
I20 5th point 228
I21 6th point 229
I22 7th point 230
I23 8th point 231
I24 9th point 232
I25 10th point 234
I26 11th point 235
I27
Sequence start
generator module
factor
1
12th point 236
I28 100ms 256
I29 40ms 255
I30 20ms 254
I31
Internal timer factor
2
10ms 253
I50 to
I255
Intelligent function
module factor
6
Specifies which intelligent
function module is used
with parameters.
18 to 223
REMARK
1 : 1st to 12th points are allocated in order, beginning from the sequence start
generator module installed closest to the High Performance model QCPU.
2 : The internal times shown are the default setting times.
These times can be designated in 0.5 ms units through a 0.5 to 1000 ms range
set at the "PLC system" tab screen in the “(PLC) Parameter" dialog box.
3 : When an error interruption with "I32 (error that stops operation)" occurs, the
High Performance model QCPU is not stopped until I32 processing is
completed.
4 : Execution of error interruptions is prohibited for the interrupt pointer Nos. I32 to
I39 when the power is turned on and during a High Performance model QCPU
reset. When using interrupt pointer Nos. I32 to I39, set the interruption
permitted status by using the IMASK instruction.
5 : Set the time-out period of the internal timer by choosing "PLC system" -
"System interrupt setting" - "High speed interrupt setting" on the PLC parameter
screen.
Set it in the setting range 0.2 to 1.0ms in 0.1ms increments.
6 : To use the intelligent function module interrupt, the intelligent function module
setting (interrupt points setting) is required at the "PLC system" tab screen in
the “(PLC) Parameter" dialog box.
(For the interrupts from the intelligent function module, see Section 8.2.1.)
POINT
7: When you have set I49 in the PLC parameters, do not execute other interrupt
programs (I0 to I48, I50 to I255) and fixed-cycle programs. If any fixed-cycle
program or like is run, the interrupt program using I49 cannot be executed at
the preset interrupt cycle intervals.