6 Programming Features
133
Stall Prevention during Operation
Stall Prevention above Base Speed during Run (n115)
The stall prevention level can be decreased automatically in the constant
output range.
n115 Settings
Acceleration/Deceleration Time Selection during Stall Pre-
vention (n116)
With this function, Acceleration Time 2 (n021) and Deceleration Time
2 (n022) can be fixed as the acceleration/deceleration time when mov-
ing to prevent stalling during operation.
Constant
No.
Name Unit Setting
Range
Factory
Setting
n115 Stall Prevention above
Base Speed during Run
- 0=Disabled
1=Enabled
0
Setting Function
0 The stall prevention level is the level set for constant n094
in all frequency areas.
1 The following figure shows how the stall prevention level is
automatically decreased in the constant output range
(Max. frequency > Max. Voltage Output Frequency
(n013)).
The lower limit is 40% of the set value of n094.
Constant
No.
Name Unit Setting
Range
Factory
Setting
n116 Acceleration/Deceleration
Time Selection during
Stall Prevention
- 0=Disabled
1=Enabled
0
Constant Output Area
Operation Level
n094
40% of n094
n013
Output Frequency
Lower Limit
n094
Max. Voltage Output Frequency n013
Operation Level
Output Frequency

Table of Contents

Other manuals for Omron VARISPEED V7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron VARISPEED V7 and is the answer not in the manual?

Omron VARISPEED V7 Specifications

General IconGeneral
BrandOmron
ModelVARISPEED V7
CategoryInverter
LanguageEnglish

Related product manuals