II - 15
Processes and Functions
SM830063
2
17.
Discharge Temperature Control (Only for U, D Type)
If the range shown below is continuously detected for 6 minutes, the unit will thermo-off operation is initiated.
1248_M_I
-2
B
A A: Thermo-off range in heating
B: Thermo-off range in cooling (drying)
Room temp.
(deg)
Discharge
Set temp.
+2
*1. The discharge temperature was factory set as follows: 15 °C for cooling; 40 °C for heating
This can be changed using the simple setting mode on the remote controller.
2. For U and D type, thermo-off operation is initiated if one of the thermo-off conditions for normal room temperature
control and the discharge temperature control is met.
18. Automatic Restart Function after Power Failure
Even when power failure occures, preset programmed operation can be reactivated once power is resumes within 100 hrs.
19. Filter Sign
Filter sign informes you when maintenance is necessary.
2,500 hrs : X, S, T, SL, type
150 hrs : AS, K, F, FM type