SM830063
I-69
1
ECO MULTI SYSTEM Unit Specifications
6-1. Specifications
Unit specifications (A)
6. Ceiling Mounted Type
MODEL No. Indoor Unit SPW-TR183GH56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 5.6 6.3
BTU / h 19,000 21,000
Air circulation (Hi / Me / Lo) m
3
/ h 780 / 660 / 540
Moisture removal (High) Liters / h 2.8 —
ELECTRICAL RATINGS
Voltage rating V 220 - 230 - 240
Available voltage range V 198 – 264
Running amperes A 0.40 - 0.40 - 0.40 0.30 - 0.30 - 0.31
Power input W 84 - 88 - 93 64 - 68 - 73
Power factor % 95 - 96 - 97 97 - 99 - 98
Fan motor locked rotor amperes A 1 - 1 - 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds (Indoor unit) 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 36 / 33 / 30
Refrigerant tubing connections Flare type
Refrigerant tube Narrow tube mm (in) 9.52 (3 / 8)
diameter Wide tube mm (in) 15.88 (5 / 8)
Drain connection 20 A, OD26 mm
Remote Controller Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories Optional / —
Color (Approximate value) Munsell 10Y9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Dimensions Height mm (in) 190 ( 7 - 15 /32) 266 (10 - 15 /32)
Width mm (in) 1,080 (42 - 17 /32) 1,183 ( 46 - 9 /16)
Depth mm (in) 670 (26 - 3 / 8) 789 (31 - 1 /16)
Net weight kg (lb) 23 ( 51 )
Shipping weight kg (lb) 28 ( 62 )
Shipping volume m
3
(cu. ft) 0.248 ( 8.76 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB