I-87
SM830063
1
ECO MULTI SYSTEM Unit Specifications
MODEL No. SPW-UR93GH56
Source 220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (1 … ø 190)
Fan motor
Model…Nominal output W KFG4X-31A3P … 30 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4 … 834
Coil resistance BRN WHT : 101.9 ORG YEL : 56.57
(Ambient temperature 20°C) WHT VLT : 17.67 YEL BLK : 366.4
VLT ORG : 7.86 ORG PNK : 38.84
Safety device
Operating temperature Open °C 130 ± 5
Close °C (115 ± 5)
Run capacitor VAC, µF 440 V, 2.5 µF
Electronic expansion valve
Coil DKV-MOZS550E0
Coil resistance (at 20°C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Valve body IKV-24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 2 … 1.5
Face area m
2
0.126
Drain pump WP20SL-9
Rated V, W AC 230 V, 50 Hz, 14.7 W
Total head & capacity 400 mm, 600 cc/min
7. Concealed Duct Type
7-2. Major component specifications
Indoor unit (A)