The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
182 System Manual, 12/2015, C79000-G8976-C253-04
Number of
indexes
occupied
DNP3 object group [vari-
ation]
(S7 data type)
Data object for receive direction
Receive max. 12 double words
(at least 1 double word) with
any information
1 ... 12
• 30 [1] (DINT)
• 30 [5] (REAL)
• 32 [1] (DINT)
• 32 [3] (DINT)
• 32 [7] (REAL)
• 40 [1] (DINT)
• 40 [3] (REAL)
• 41 [1] (DINT)
• 41 [3] (REAL)
• 1 ... 5
• 5
• 1 ... 3
• 4 ... 5
• 5
• 1 ... 5
• 5
• 1 ... 5
• 5
• M
• M
• M
• M
• M
• S
• S
• S
• S
2 ... 24
• 30 [2] (INT, WORD)
• 32 [2] (INT, WORD)
• 32 [4] (INT, WORD)
• 40 [2] (INT, WORD)
• 41 [2] (INT, WORD)
• 1 ... 5
• 1 ... 3
• 4 ... 5
• 1 ... 5
• 1 ... 5
• M
• M
• M
• S
• S
4 ... 48
• 30 [2] (BYTE)
• 32 [2] (BYTE)
• 32 [4] (BYTE)
• 40 [2] (BYTE)
• 41 [2] (BYTE)
• 110 [1..255] (CHAR)
• 111 [1..255] (CHAR)
• 1 ... 5
• 1 ... 3
• 4 ... 5
• 1 ... 5
• 1 ... 5
• 1 ... 5
• 1 ... 5
• M
• M
• M
• S
• S
• M / S
• M
Objects for data exchange with MODBUS slaves (only in station)
Write data from the station
Read data from the MODBUS
Data objects not supported
Par12x1D_R Cannot be used for the DNP3
DNP3 implementation level that must be supported by the communications partner.
Station type: M = master station TIM, S = station TIM
These objects are used to mirror back values from the station to the master station, see the following reference.
The following objects are always sent by the master TIM with the control code "DIRECT_OPERATE": Bin08X_S (12),
Cmd01B_S (12), Par12D_S (41), Set01W_S (41)
Mirroring back: You will find an description of the function in the section in the section
Mirroring back (Page 183).
You will find a table sorted according to DNP3 object groups in the section Supported DNP3
object groups (Page 162).