Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
281
Diagnostic messages of the TIM
Classification of TIM messages
The TIM uses a reserved area within the event class F, namely Fx60, known as the event ID.
All TIM diagnostics messages start with Fx60 in the hexadecimal representation, where x a
digit is the placeholder for an identifier that allows a global classification of the message:
Table 7- 3 Global classification of the TIM diagnostic messages
Event message, exiting state
Event message, entering state
Event message, internal error, exiting state
5 F560 Event message, internal error, entering state
Event message, external error, exiting state
Event message, external error, entering state
The event ID Fx60 is followed by the actual message, the detailed event. This occupies the
numeric range from 0000h to 0FFFh. Depending on the message, there may be additional
information under
Additional info 1/2/3
or
Additional info 4/5
.
The diagnostic messages of the TIM in hexadecimal and plain text format
The following table lists all the TIM diagnostic messages in ascending order of the detailed
event in hexadecimal format.
To complete the picture, the corresponding event ID is also listed. The event ID is used only
to classify the message and has no relevance for the order.
Table 7- 4 Diagnostic messages of the TIM
0001
Entering state: Heap memory overflow.
Exiting state: Heap memory overflow eliminated.
DNP3 installation started.
Error creating the message queue of the INIT task.
Error installing the DNA interrupt service routine.
Error installing the interrupt service routine for the external interface.
Error installing the interrupt service routine for the internal interface.
Error installing the TIMER interrupt service routine.
Structure of the interface administration could not be entered in the catalog.