The SINAUT Configuration Tool
6.8 Changing the configuration
TIM DNP3
238 System Manual, 12/2015, C79000-G8976-C253-04
Object affected
Action in the SINAUT configu-
ration tool
Necessary follow-up action
Network nodes Changing the parameter set-
tings of a network node
The SDBs of the module that contains this network node must
be regenerated.
Network nodes
Networking a network node
-
Network nodes Deleting a network node All telecontrol connections running via this network node are
then invalid and are removed the next time you open the con-
nection configuration. When necessary, these must be replaced
by alternative connections. The SDBs or DBs of all modules that
were involved in these deleted connections must be regenerat-
ed in the subscriber administration.
Network nodes Canceling the networking of a
network node
All telecontrol connections running via this network node are
then invalid and are removed the next time you open the con-
nection configuration. When necessary, these must be replaced
by alternative connections. The SDBs or DBs of all modules that
were involved in these deleted connections must be regenerat-
ed in the subscriber administration.
Telecontrol connection Adding a telecontrol connec-
tion
The SDBs or DBs of all subscribers over which this connection
runs must be regenerated in the subscriber administration.
Telecontrol connection Deleting a telecontrol connec-
tion
The SDBs or DBs of all subscribers over which the deleted
connection runs must be regenerated in the subscriber admin-
istration.
Telecontrol subscriber Changing the parameter set-
tings of a subscriber
The SDBs or DBs of all connections that run over this subscrib-
er must be regenerated in the subscriber administration.
Destination subscriber
properties of TD7onTIM
Changing the parameter set-
tings of the destination sub-
scriber properties of a
destination subscriber of
TD7onTIM
The SDBs of all TIMs with TD7onTIM that communicate with
this destination subscriber must be regenerated in subscriber
administration.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TIM 3V-IE DNP3 and is the answer not in the manual?

Siemens SIMATIC TIM 3V-IE DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TIM 3V-IE DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals