Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
279
● To use this function, the firmware must have been installed on the computer using the
setup. If the firmware is not installed on the PG or is incomplete, a message is displayed.
● By clicking the
Installation details
button, you open the
Update details
dialog that displays
the firmware version installed on the TIM module and the version on your computer.
● You can read out the required version of the operating system of a TIM using the
Module
Information
function /
General
tab.
Repairing involves the following steps:
● The flash disk of the TIM module is formatted. After formatting, the TIM module runs a
reset.
● This is followed by a default startup.
● Once the wait time for the default startup has elapsed, the firmware version installed on
the computer is downloaded to the TIM.
● Following this, the system data blocks are transferred to the TIM module.
● The module is then reset and resumes operation with its full functionality.
Note
You can download the new firmware via Ethernet or the MPI i
nterface.
If you download the firmware using the MPI interface (TIM as a CP in the S7
-300), then
during the new installation of the firmware, the TIM module uses MPI address 3. Make
sure that this address is free on the MPI bus to which the TIM module is c
onnected.
Note
Make sure that you select the correct TIM module in your project. The station and module
name must match and the configured module must be of the same type as the module to
which you are downloading.
If this is not the case, a dialog will inform you of this at regular intervals during the update.
The display of this message interrupts the update until the dialog is acknowledged by
clicking on
OK
.
1. Make sure that MPI address 3 is either free or is occupied by the module on which you
want to install.
2. Select the TIM you want to repair in the
SINAUT subscriber list
of the open project.
3. Start the function by selecting the
SINAUT / Repair
menu and then
Complete
reinstallation
in the context menu. The
Firmware Install
dialog opens. The version
installed on the PG is displayed. If the firmware on the PG is incomplete, a message to
this effect is also displayed.