EasyManuals Logo
Home>Siemens>Control Unit>SIMATIC TIM 3V-IE DNP3

Siemens SIMATIC TIM 3V-IE DNP3 User Manual

Siemens SIMATIC TIM 3V-IE DNP3
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
Uses and properties of the TIM
1.10 Configuration limits
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
29
Table 1- 2 Overview of the connection resources
TIM type
Subscriber type /
interface configura-
tion
Max. number of
connections per
TIM in total
Interface
Network type
Max. number of
connections per
interface
TIM 4R-IE DNP3 Master station 128
*
Ethernet 1
TCP
64
Ethernet 2 TCP 64
RS232 no. 1
Dedicated line
32
Dial-up network
32
RS232 no. 2
Dedicated line
32
Dial-up network
32
Station 32
Ethernet 1
TCP
16
Ethernet 2
TCP
16
RS232 no. 1
Dedicated line
16
Dial-up network
16
RS232 no. 2
Dedicated line
16
Dial-up network
16
TIM 3V-IE DNP3 Master station /
node station
8
Ethernet
TCP
8
RS232
Dedicated line
8
Dial-up network
8
Station 8
Ethernet
TCP
8
RS232
Dedicated line
8
Dial-up network
8
*
The total number of 128 also applies to the TIM 4R IE DNP3 as a node station. The maximum number per interface is
obtained from the information in the "Master station" or "Station" rows.
Number of communications objects per TIM
The maximum number of communications objects for DNP3 communication per TIM is 100.
Size of the message memory for events
TIM 3V-IE DNP3: 64 000 events
TIM 4R-IE DNP3: 200 000 events

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TIM 3V-IE DNP3 and is the answer not in the manual?

Siemens SIMATIC TIM 3V-IE DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TIM 3V-IE DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals