Configuration in STEP 7
5.1 Overview
TIM DNP3
82 System Manual, 12/2015, C79000-G8976-C253-04
Configuration in the SINAUT configuration tool
If the system is networked and the properties for the networks or network nodes have been
specified, the SINAUT configuration tool is called.
Image 5-5 SINAUT configuration tool for connection configuration and subscriber administration
●
Configuration of the telecontrol connections
Open the connection configuration in the SINAUT configuration tool. Here, the
connections that are possible from the PC of the control center to the CPU are identified
and made available for selection.
Select the required connections from the right-hand pane of the connection configuration
and drag them to the left-hand pane.
●
Configuring the subscribers
After saving the selected connections, you then open Subscriber administration. Here,
the connections or the subscriber number can be changed.
All CPUs, PC(s) of the control center and all TIMs are also assigned a subscriber number
(DNP3 address) that is unique throughout the system. If no further changes are
necessary, this is followed by configuration of the TD7 software.