Service cases - hardware
4.4 Machine control panels
Hardware and Software
Service Manual, 03/2011, 6FC5397-5DP40-0BA0
99
Procedure:
1. Switch-off the control: Completely switch off the system. Check that the system is in a no-
voltage condition and is locked-out so that it cannot be switched on again without the
appropriate authorization.
2. Access the operator panel/control cabinet in which the machine control panel is located.
3. Using a multimeter, check the X10 power supply to ensure that the system really is in a
no-voltage condition.
4. If it has not already been done, label all connectors that lead to the module now.
Only then, can it be ensured that the cables are not interchanged.
5. Withdraw the power supply X10 (
⑭).
6. Release the strain relief of the Ethernet cable (
⑨)
7. Remove the Ethernet cables from the X20 / X21 interface (port 1/port 2) (
④)
8. Release other cables (e.g. the Emergency Stop cable or the button from the mini
handheld unit or from other command devices), if available.
9. Remove the ground connection by releasing the grounding screw (
①).
10. Release the machine control panel from the control panel by releasing the clips.
11. Note down the set address S2 (
⑪) at the DIL switch of the defective module.
4.4.6 This is how you install the MCP 483C PN
Installing
Procedure:
1. Set DIL switch S2 (
⑪) of the new module to what you previously noted down.
2. Installing a new machine control panel.
3. Secure the clips to retain the machine control panel and tighten them.
4. Connect the ground connection (
①).
5. Reconnect the other cables (e.g. the Emergency Stop cable or the button from the mini
handheld unit or from other command devices), if available.
6. Reinsert the Ethernet cables at the X20/X21 interface (port 1/port 2) (
④).
7. Re-establish the Ethernet cable strain relief (
⑨).
8. Reconnect the power supply X10 (
⑭).
9. Close the cabinet and switch-on the system again.