First Steps
Electrical Inspection
Device Protection
!
DANGER
Danger when connecting the SIPROTEC 5 device
Noncompliance with the safety notes will result in death, severe injury or considerable material
damage.
²
The device must be situated in the operating area for at least 2 hours before you connect it to the
power supply for the first time. This prevents condensate from forming in the device.
²
If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2
days. This will cause the electrolytic capacitors on the printed circuit-board assemblies to form again.
²
Perform the electrical inspection.
Activating the Battery
i
i
NOTE
The battery is covered by a protective film, which also prevents premature discharge.
The battery compartment is located on the rear of the base module. You do not have to take the battery
out of the compartment in order to remove the protective film.
²
Pull out the battery compartment including the battery.
²
Remove the protective film from the battery by simply pulling on the film tab.
²
Push the battery compartment including the battery back in again.
Grounding a Device
The SIPROTEC 5 devices are protection class I equipment must be connected with the system ground prior to
commissioning.
²
Ground each module with solid low-impedance system grounding (cross-section ≥ 4.0 mm
2
(≥ 0.0062 in
2
), grounding area ≥ M4, torque: at least 1.2 Nm).
Connecting a Device
²
Connect all cables and lines. Use the connection diagrams in the Hardware and Device manuals.
²
Tighten the terminal screws to the prescribed torques (see chapter Tightening Torques for Terminal
Screws, Page 213).
Grounding an On-Site Operation Panel
²
Join several on-site operation panels to one another with firm contact.
Siemens recommends the use of contact washers on painted metal mounting walls. If the mounting wall
is not metallic, place a metal layer, for example a metal sheet, between the mounting wall and the on-
site operation panels. Then connect this sheet to the system grounding.
5.1
5.1.1
Working on the Device
5.1 First Steps
154 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 5
CategoryController
LanguageEnglish

Related product manuals