Page #89 background image
[tdio212x, 1, en_US]
Figure 3-48
IO212 – Connection Diagram
Input and Output Module IO214
Description
This input and output module is used as the base measurement module in all protection devices. One device
can contain several IO214 input and output modules. The number of IO214 input and output modules
depends on the measured values required. Up to 40 measuring channels are possible for each SIPROTEC
device.
The terminals for the following are located on the input and output module IO214:
4 current transformers (optionally protection-class current transformers or instrument transformers)
4 voltage transformers
2 binary inputs
5 binary outputs with 4 high-speed make contacts (type F) and 1 high-speed change-over contact (type
F)
The connections are distributed over:
1 x 8-pole current terminal
3 x 14-pole voltage terminal
3.2.14
3.2.14.1
Electronic Modules
3.2 Input and Output Modules of the Modular Devices
SIPROTEC 5, Hardware Description, Manual 89
C53000-G5040-C002-C, Edition 10.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 5
CategoryController
LanguageEnglish

Related product manuals