Functions
2.25 Function Control and Circuit Breaker Test
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
461
2.25.3.4 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
2.25.3.5 Information List
Addr. Parameter Setting Options Default Setting Comments
610 FltDisp.LED/LCD Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
615 Spont. FltDisp. NO
YES
NO Spontaneous display of flt.annun-
ciations
625A T MIN LED HOLD 0 .. 60 min; ∞ 0 min Minimum hold time of lachted
LEDs
640 Start image DD image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default Display
No. Information Type of In-
formation
Comments
- Test mode IntSP Test mode
- DataStop IntSP Stop data transmission
- UnlockDT IntSP Unlock data transmission via BI
- Reset LED IntSP Reset LED
- SynchClock IntSP_Ev Clock Synchronization
- >Light on SP >Back Light on
- HWTestMod IntSP Hardware Test Mode
- Error FMS1 OUT Error FMS FO 1
- Error FMS2 OUT Error FMS FO 2
- Distur.CFC OUT Disturbance CFC
- Brk OPENED IntSP Breaker OPENED
- FdrEARTHED IntSP Feeder EARTHED
3 >Time Synch SP >Synchronize Internal Real Time Clock
5 >Reset LED SP >Reset LED
11 >Annunc. 1 SP >User defined annunciation 1
12 >Annunc. 2 SP >User defined annunciation 2
13 >Annunc. 3 SP >User defined annunciation 3
14 >Annunc. 4 SP >User defined annunciation 4
15 >Test mode SP >Test mode
16 >DataStop SP >Stop data transmission
51 Device OK OUT Device is Operational and Protecting
52 ProtActive IntSP At Least 1 Protection Funct. is Active
55 Reset Device OUT Reset Device
56 Initial Start OUT Initial Start of Device
60 Reset LED OUT_Ev Reset LED
67 Resume OUT Resume