Functions
2.2 Protection Data Interfaces and Protection Data Topology
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
89
2.2.3.3 Information List
4615A PI2 BLOCK UNSYM YES
NO
YES Prot.2: Block. due to unsym. delay
time
4801 GPS-SYNC. ON
OFF
OFF GPS synchronization
4803A TD GPS FAILD 0.5 .. 60.0 sec 2.1 sec Delay time for local GPS-pulse
loss
No. Information Type of In-
formation
Comments
3215 Wrong Firmware OUT Incompatible Firmware Versions
3217 PI1 Data reflec OUT Prot Int 1: Own Datas received
3218 PI2 Data reflec OUT Prot Int 2: Own Datas received
3227 >PI1 light off SP >Prot Int 1: Transmitter is switched off
3228 >PI2 light off SP >Prot Int 2: Transmitter is switched off
3229 PI1 Data fault OUT Prot Int 1: Reception of faulty data
3230 PI1 Datafailure OUT Prot Int 1: Total receiption failure
3231 PI2 Data fault OUT Prot Int 2: Reception of faulty data
3232 PI2 Datafailure OUT Prot Int 2: Total receiption failure
3233 DT inconsistent OUT Device table has inconsistent numbers
3234 DT unequal OUT Device tables are unequal
3235 Par. different OUT Differences between common parameters
3236 PI1<->PI2 error OUT Different PI for transmit and receive
3239 PI1 TD alarm OUT Prot Int 1: Transmission delay too high
3240 PI2 TD alarm OUT Prot Int 2: Transmission delay too high
3243 PI1 with VI Prot Int 1: Connected with relay ID
3244 PI2 with VI Prot Int 2: Connected with relay ID
3245 >GPS failure SP > GPS failure from external
3247 GPS loss OUT GPS: local pulse loss
3248 PI 1 GPS sync. OUT GPS: Prot Int 1 is GPS sychronized
3249 PI 2 GPS sync. OUT GPS: Prot Int 2 is GPS sychronized
3250 PI 1 PD unsym. OUT GPS:PI1 unsym.propagation delay too high
3251 PI 2 PD unsym. OUT GPS:PI2 unsym.propagation delay too high
3252 >SYNC PI1 RESET SP > PI1 Synchronization RESET
3253 >SYNC PI2 RESET SP > PI2 Synchronization RESET
3254 PI1 jump OUT Prot.1: Delay time change recognized
3255 PI2 jump OUT Prot.2: Delay time change recognized
3256 PI1 unsym. IntSP Prot.1: Delay time unsymmetry to large
3257 PI2 unsym. IntSP Prot.2: Delay time unsymmetry to large
3258 PI1 Error OUT ProtInt1:Permissible error rate exceeded
3259 PI2 Error OUT ProtInt2:Permissible error rate exceeded
3274 PI1: C37.94 n/a OUT PI1: IEEE C37.94 not supported by module
3275 PI2: C37.94 n/a OUT PI2: IEEE C37.94 not supported by module
Addr. Parameter Setting Options Default Setting Comments

Table of Contents