EN
ATYSp - 542001E - SOCOMEC
AnnexeII-23.Product counters
Function 3 Codes
Dec.
Address
Hex.
Address
Words
count
Description Unit
23552 5C00 1 Total Cycles counter nb of cycles
23553 5C01 1 Total Position 0 switches counter nb of operations
23554 5C02 1 Total Position I switches counter nb of operations
23555 5C03 1 Total Position II switches counter nb of operations
23556 5C04 1 Total switches counter nb of operations
23557 5C05 1 Cycles in auto mode (including control mode) counter nb of cycles
23558 5C06 1 Position 0 switches in auto mode (including control mode) counter nb of operations
23559 5C07 1 Position I switches in auto mode (including control mode) counter nb of operations
23560 5C08 1 Position II switches in auto mode (including control mode) counter nb of operations
23561 5C09 1 Total switches in auto mode (including control mode) counter nb of operations
23562 5C0A 1 Cycles in manual mode counter nb of cycles
23563 5C0B 1 Position 0 switches in manual mode counter nb of operations
23564 5C0C 1 Position I switches in manual mode counter nb of operations
23565 5C0D 1 Position II switches in manual mode counter nb of operations
23566 5C0E 1 Total switches in manual mode counter nb of operations
23567 5C0F 1 Cycles in control mode counter nb of cycles
23568 5C10 1 Position 0 switches in control mode counter nb of operations
23569 5C11 1 Position I switches in control mode counter nb of operations
23570 5C12 1 Position II switches in control mode counter nb of operations
23571 5C13 1 Total switches in control mode counter nb of operations
23572 5C14 2 Product power on time s
23574 5C16 1 Start order activation counter nb of operations
23575 5C17 2 Start order active duration s
23577 5C19 2 Secondary source presence duration s
23579 5C1B 2 Secondary source active (i.e. present and switch position at
secondary source) duration
s
23581 5C1D 2 Source 1 load supplied duration s
23583 5C1F 2 Source 2 load supplied duration s
AnnexeII-24.Output set
Function 3, 6 and 16 Codes
Dec.
Address
Hex.
Address
Words
count
Description Unit
23632 5C50 1 OUT1 - Option Module1 Output1 logical state
0: Not active
1: Active
23633 5C51 1 OUT2 - Option Module1 Output2 logical state
0: Not active
1: Active
23634 5C52 1 OUT3 - Option Module2 Output1 logical state
0: Not active
1: Active