EN
ATYSp - 542001E - SOCOMEC
16. CHARACTERISTICS
Characteristics according to IEC 60947-3 and IEC 60947-6-1
125 to 630 A
ThermalcurrentI
th
to 40°C 125 A 160 A 200 A 250 A 315 A 400 A 500 A 630 A
Rated insulation voltage Ui (V) (power circuit) 800 800 800 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (kV) (power circuit) 8 8 8 12 12 12 12 12
Rated insulation voltage Ui (V) (control circuit) 300 300 300 300 300 300 300 300
Rated impulse withstand voltage Uimp (kV) (control circuit) 4 4 4 4 4 4 4 4
Rated operational currents I
e

Ratedvoltage Utilisationcategory A/B A/B A/B A/B A/B A/B A/B A/B
415 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 250/250 315/315 400/400 500/500 630/630
415 VAC AC-22 A / AC-22 B 125/125 160/160 200/200 250/250 315/315 400/400 500/500 630/630
415 VAC AC-23 A / AC-23 B 125/125 160/160 200/200 200/200 315/315 400/400 500/500 500/630
500 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 250/250 315/315 400/400 500/500 630/630
500 VAC AC-22 A / AC-22 B 125/125 160/160 200/200 200/250 200/315 200/400 500/500 500/500
500 VAC AC-23 A / AC-23 B 80/80 80/80 80/80 200/200 200/200 200/200 400/400 400/400
690 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 200/200 200/200 200/200 500/500 500/500
690 VAC AC-22 A / AC-22 B 125/125 125/125 125/125 160/160 160/160 160/160 400/400 400/400
690 VAC AC-23 A / AC-23 B 63/80 63/80 63/80 125/125 125/125 125/125 400/400 400/400
220 VDC DC-21 A / DC-21 B 125/125 160/160 200/200 250/250 250/250 250/250 500/500 630/630
220 VDC DC-22 A / DC-22 B 125/125 160/160 200/200 250/250 250/250 250/250 500/500 630/630
220 VDC DC-23 A / DC-23 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
440 VDC
(1)
DC-21 A / DC-21 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
440 VDC
(1)
DC-22 A / DC-22 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
440 VDC
(1)
DC-23 A / DC-23 B 125/125 125/125 125/125 200/200 200/200 200/200 500/500 630/630
Rated operational currents I
e

Ratedvoltage Utilisationcategory
415 VAC AC-31 B 125 160 200 250 315 400 500 630
415 VAC AC-32 B 200 315 400 500 500
415 VAC AC-33 B 200 200 200 400 400

Prospective fuse protected short-circuit withstand at 415 VAC(6) 100 100 50 50 50 50 50 50
Prospective fuse protected short-circuit withstand at 690 VAC(kA rms) / / / 50 50 50 50 50
Associated fuse rating (A) 125 160 200 250 315 400 500 630

Current rated as short-time withstand I
cw
0,3s, 415 VAC (kA rms) 12 12 12 15 15 15 17 17
Current rated as short-time withstand I
cw
0,3s, 690 VAC (kA rms) / / / 15 15 15 17 17
Current rated as short-time withstand I
cw
1s, 415 VAC (kA rms) 7 7 7 8 8 8 10 10
Current rated as short-time withstand I
cw
1s, 690 VAC (kA rms) / / / 8 8 8 10 10
Power rated as closing short-circuit I
cm
at 415 VAC (peak kA) 11.9 11.9 11.9 22 22 22 17 17

Current rated as short-time withstand I
cw
30 ms (kA rms), 415 VAC 10 10 10 10 10 10 / /
Current rated as short-time withstand I
cw
60 ms (kA rms), 415 VAC / / / / / / 10 12.6
Power rated as closing short-circuit I
cm
at 415 VAC (peak kA) 17 17 17 17 17 17 17 25
Connection
Minimum Cu cable cross-section as per IEC 60947-1 (mm²) 35 35 50 95 120 185 2 x 95 2 x 120
Recommended Cu busbar cross-section (mm²) 2 x 32 x 5 2 x 40 x 5
Maximum Cu cable cross-section (mm²) 50 95 120 150 240 240 2 x 185 2 x 300
Maximum Cu busbar width (mm) 25 25 25 32 32 32 50 50
Min./max. tightening torque (Nm) 9/13 9/13 9/13 20/26 20/26 20/26 40/45 40/45

Time of transfer I-II or II-I (s) 0.85 0.85 0.85 0.9 0.9 0.9 0.95 0.95
I-0 or II-0 (s) 0.55 0.55 0.55 0.5 0.5 0.5 0.55 0.55
Time of contact transfer ("black-out" I-II) minimum (s) 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4
Power supply
Min./max. power (VAC) 166/332 166/332 166/332 166/332 166/332 166/332 166/332 166/332
Control supply power demand
Demand/rated power (VA) - ATyS r, ATyS d 184/92 184/92 184/92 276/115 276/115 276/115 276/150 276/150
Demand/rated power (VA) - ATyS t, g , p 206/114 206/114 206/114 298/137 298/137 298/137 298/172 298/172
Mechanical specifications
Durability (number of operating cycles) 10,000 10,000 10,000 8,000 8,000 8,000 5,000 5,000
Weight ATyS r 3 P / 4 P (kg) 5.7/ 6.9 5.7/ 6.9 5.7/ 6.9 6.6/ 7.4 6.7/ 7.8 6.7/ 7.8 11.4/ 13.3 11.9/ 14.0
Weight ATyS d 3 P / 4 P (kg) 6.3/ 7.5 6.3/ 7.5 6.3/ 7.5 7.2/ 8.0 7.3/ 8.4 7.3/ 8.4 12.0/ 13.9 12.5/ 14.6
Weight ATyS t, g, p 3 P / 4 P (kg) 6.8/ 8.0 6.8/ 8.0 6.8/ 8.0 7.7/ 8.5 7.8/ 8.9 7.8/ 8.9 12.5/ 14.4 13.0/ 15.1
(1) 3-pole device with 2 „+“ poles in series and 1 „-“ pole. 4-pole device with 2 poles in series by polarity

Table of Contents

Other manuals for socomec ATyS s

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS s and is the answer not in the manual?

socomec ATyS s Specifications

General IconGeneral
Brandsocomec
ModelATyS s
CategorySwitch
LanguageEnglish

Related product manuals