EN
ATYSp - 542001E - SOCOMEC
Customer input autotest failed No
Abnormal switching when not in manual mode Yes
Requested position not reached Yes
Locked mode active when not in manual mode Yes
External Fault -> User input No
Unexpected current owing through the motor when idle Yes
Sampling rate for the above is every 10 ms
Exception: motor detection sampling rate is every 5 min
Technical data
Auxiliary Contact Quantity 4
Conguration NO
Mechanical Endurance 100k cycles
Response Time 5 – 10 ms
Startup duration 200ms
Rated Voltage / Switching Voltage 250VAC
Rated Current 2A
Surge protectionVin_sg: 4.8kV (1.2/50µs surge)
ESD withstand voltage (Contact/air): 2/4kV
Dielectric Strength contact/parts: 4.8kVAC (Reinforced Insulation)
Insulation: 4.8KVAC
Output Terminal: 1.5mm
2
minimum / 2.5mm
2
maximum
8.2.6.Programmabledrycontactoutput
Pin63B–64B: Output Out1
Output "Out1", Programmable Output 1 is set by default as a
Product Available Output for the ATS controller module.
To achieve a single product feedback connect this contact in series
with 63A 64A. (Normally Open contact that is held closed when the
ATS is available). Being programmable this output may be changed to
any other normally open or normally closed output as available in the
product.
NOTE: Details of the programmable outputs, see page 97.
ATS Module
Output Contact
(Programmable)
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
To D10
To D20
64B 63B
64B 63B
417 416 415 414 413
207 208 209 210
417 416 415 414 413
207 208 209 210
7172 74
7172 74
ATyS t
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS p
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS g
The ATySp may accept a total of 4 additional Input / Output modules
offering an additional 8 programmable inputs and 8 programmable
outputs.
Refer to accessory section for details:
Note:
For pulsed outputs and 4-20mA output refer to specic optional module instruction manuel on www.socomec.com.

Table of Contents

Other manuals for socomec ATyS s

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS s and is the answer not in the manual?

socomec ATyS s Specifications

General IconGeneral
Brandsocomec
ModelATyS s
CategorySwitch
LanguageEnglish

Related product manuals