ATYSp - 542001E - SOCOMEC
Dec.
Address
Hex.
Address
Words
count
Description Unit
57632 E120 1 Gateway External MODBUS Parity
0: none
1: even
2: odd
57633 E121 1 Gateway External MODBUS Stopbit
0: 1 stop bit
1: 2 stop bits
57634 E122 1 MODBUS Gateway Master request timeout ms
57635 E123 1 MODBUS Slave address (RS485 & RTU over Ethernet) 1-247
AnnexeII-8.Actionsystem
Function 6 Codes
Dec.
Address
Hex.
Address
Words
count
Description Unit
57856 E200 1 Action:
0xA1: Product Conguration storage
0xB2: Produit reset
AnnexeII-9.Status
Function 3 Codes
Dec.
Address
Hex.
Address
Words
count
Description Unit
20480 5000 2 Date & Time Current -
20482 5002 1 Opearting Mode
0x0000: Manual Mode
0x0001: Locked Mode
0x0010: Auto Mode
0x0020: Remote control mode
0x0040: Inhibit Mode
20483 5003 1 Switch Position
0: Unknown
1: Position 0
2: Position I
3: Position II
20484 5004 1 Source 2 Start Generator relay State
0: Not Active
1: Active
20485 5005 1 Priority
0: Network
1: Source 1
2: Source 2
20486 5006 1 Source1 State
0: Under Threshold BusBar
1: Present
2: Available
20487 5007 1 Source2 State
0: Under Threshold BusBar
1: Present
2: Available
20488 5008 1 Test in progress
0x0000: None
0x0001: TOF
0x0002: EOF
0x0004: TON
0x0008: EON

Table of Contents

Other manuals for socomec ATyS s

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS s and is the answer not in the manual?

socomec ATyS s Specifications

General IconGeneral
Brandsocomec
ModelATyS s
CategorySwitch
LanguageEnglish

Related product manuals