AnnexeI-6.Setupmenu–keypadnavigation
1
SETUP
Definition AdjustmentRange M-G M-M
NETWORK 4NBL
Network Type 1BL/2BL/2NBL/3BL/3NBL
4BL/4NBL/41NBL/42NBL
AUTOCONF NO
Auto Conguration: (visible in manual mode)
Network Voltage, Frequency, phase rotation
and neutral position
NO
YES
NEUTRAL AUTO
Neutral Position: visible if the makes sense
with the seleted network type.
Neutral xed on the LEFT - (N, L3, L2, L1)
Neutral xed on the RIGHT - (L1, L2, L3, N)
Auto Detection of Neutral LEFT or RIGHT
LEFT
RIGHT
AUTO
ROT PH. ---
Select and Verify Phase Rotation as:
compatible between S1 and S2, ABC or ACB
visible if the makes sense with the seleted
network type.
It is also possible to check for consistency of
direction of rotation between 2 sources (----).
(Refer to ** Phase Rotation Check” below for
details). Both supply sources must be present
for this verication.
ABC
ACB
----
NOM. VOLT 400 V
Nominal Network Voltage 1BL: 208-332V
2NBL: 416-600V
Others: 360-575V
NOM. FREQ 50 Hz
Nominal Network Frequency 50Hz
60Hz
APP M-G
Application Type:
M – G: Main Network to Genset Supply
M – M: Main to Main Supply
M – G
M - M
PRIO TON NO
In case of a Test On Load sequence, in case
source 2 is no longer available you may:
NO - Exit the test and switch to source 1
YES - Stay in position II
Note: The MSR input (refer to I/O Menu) takes
priority over this parameter.
NO
YES
PRIO EON NO
In case of an External Test On Load, in case
source 2 is no longer available you may:
NO - Exit the test and switch to source 1
YES - Stay in position II
Note: The MSR input (refer to I/O Menu) has
priority over this parameter.
NO
YES
PRIO NET 1
This is to dene the priority network:
1: Network 1 has priority
2: Network 2 has priority
0: Neither network has priority
Note: The PRI input (refer to menu I/O) has
priority over this parameter.
(Main – Main applications)
1
2
0
RETRANS NO
Inhibit the automatic retransfer:
NO: Automatic retransfer to the priority
source
YES: "Valid" or input RTC must be pressed to
execute the return to priority.
NO
YES
CT PRI 0000
Current Transformer primary rating 1 to 3200 A

Table of Contents

Other manuals for socomec ATyS s

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS s and is the answer not in the manual?

socomec ATyS s Specifications

General IconGeneral
Brandsocomec
ModelATyS s
CategorySwitch
LanguageEnglish

Related product manuals