ATYSp - 542001E - SOCOMEC
8.2.3.Fixedinputs
Description
The ATySp includes for 5 off xed inputs through a 6 pin connector installed
on the motorisation module. No additional power supply should be used on
these contacts as the inputs MUST be used with the common supply taken
from terminal 317.
At least one of the ATySp aux power supplies (101 – 102 or 201 - 202) must
be available to activate these inputs.
Pulse duration for activation of contact inputs: ≥ 60ms.
• Pin312:Remote Control Mode Enable when closed with 317.
This contact must be closed with 317 so as to activate all control inputs except for 313 that takes priority and
is active immaterial of the state of input 312. Enabling remote control through 312 activates the remote control
inputs whilst inhibiting the ATS module automation.
• Pin313: Position 0 order if closed with 317 when in AUTO. (ForcetheswitchtotheOFFPosition)
This is a “Priority Order Input” meaning that when closed with 317 it takes priority over all other electrical
commands. The ATySp will remain in 0 position as long as the contact 313 – 317 remains closed. Once the
contact is open the ATySp is ready to receive new orders. This contact order is independent of other inputs
and is also enabled without 312 connected to 317. Impulse duration to activate and start switching to position
O is a minimum of 60ms. The product state will be unavailable.
• Pin314: Position II order if closed with 317.
This contact is active with the ATySp in AUT mode with contact 312 – 317 closed and 313 – 317 open.
Impulse duration to activate and switch to position II is a minimum of 60ms.
• Pin315: Position I order if closed with 317
This contact is active with the ATySp in AUT mode with contact 312 – 317 closed and 313 – 317 open.
Impulse duration to activate and switch to position I is a minimum of 60ms.
• Pin316: Position 0 order if closed with 317
This contact is active with the ATySp in AUT mode with contact 312 – 317 closed and 313 – 317 open.
Impulse duration to activate and switch to position O is a minimum of 60ms. For contactor logic maintain
contacts on between terminal 316 and 317.
• Pin317: Common
Common supply for inputs 312 to 316