ATYSp - 542001E - SOCOMEC
5.4. Environmental
The ATySp product meets the following environmental requirements:
5.4.1. IPRating
ø 1 mm
• IP2X against direct contact for the ATySp motorization control unit.
• IP2X against direct contact for the power section with the connections in place and when including suitable,
correctly installed incoming and outgoing terminal shields.
• IP 0 for the bare power section without terminal shields in place.
5.4.2. OperatingConditions
Temperature
• From -20 to +40°C without derating
• From -20 to +70°C when applying a Kt derating correction factor
Kt: Correction Factor Temperature
0.9 40°C … 50°C
0.8 50°C … 60°C
0.7 60°C … 70°C
* Simplied derating method: Ithu ≤ Ith x Kf
* A more precise calculation may be done for specic applications. Should this be required please contact SOCOMEC.
Hygrometry
• 80% humidity without condensation at 55°C
• 95% humidity without condensation at 40°C
Altitude
• Up to 2000m in altitude without derating
• For higher altitude the Ka correction factors below apply
Ka: Correction Factor
Ue 0.95 0.8
Ie 0.85 0.85
5.4.3. StorageConditions
Temperature
• From -40 to +70°C