8.2.Electrical operation
8.2.1.Dual power supply
The ATySp includes a dual power supply and is to be powered between terminals 101 - 102 and 201 – 202 (2
different supplies - main & alternative) within the limits of: 208 – 277VAC ± 20% / 50/60Hz ± 10%.
Current Input: 100mA (Standby mode) / 15A max (during switching mode)
Surge Protection: Vin_sg: 4.8KV – 1.2/50µs according to IEC 61010-1
Terminal connectors: Minimum 1.5mm² / Maximum 2.5mm²
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
To D10
To D20
64B 63B
64B 63B
417 416 415 414 413
207 208 209 210
417 416 415 414 413
207 208 209 210
7172 74
7172 74
ATyS t
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS p
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS g
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
To D10
To D20
64B 63B
64B 63B
417 416 415 414 413
207 208 209 210
417 416 415 414 413
207 208 209 210
7172 74
7172 74
ATyS t
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS p
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS g
201-L/N
202-N/L
101-L/N
102-N/L
Aux Supply-2
Power-230V
208-277 Vac ±20%
(166-332Vac)
Aux Supply-1
Power-230V
208-277 Vac ±20%
(166-332Vac)
8.2.2.Voltagesensinginputs
The ATySp includes dual single phase and three phase voltage sensing (terminals 103 - 106 and 203 - 206) designed
to monitor 1Phase (L-N) supplies of up to 332VAC and 3 phase (L-L) of up to 600VAC.
The ATySp is designed to handle single phase, three phase with neutral as well as three phase without neutral
networks. Simply dene the correct conguration of single or three phase during conguration through the keypad
or using Easy Cong software.
Sensing connections are usually tapped directly off the ATySp power terminals using the ATyS sensing kit available
as an accessory. Sensing kits are available with the neutral on the left or neutral on the right to match the network
conguration where the ATyS will be operating. Refer to the ATyS accessory section for more details.
(Note: Reversal of the neutral position from left to right and vice versa may also be done through the ATySp conguration settings).
Sensing values measured will have a direct inuence on determining the availability of the main and the alternative
supplies as well as the ATySp automation.
The parameters monitored through sensing are the following:
•
Phase imbalance in the ATySp is relative to the nominal voltage congured in the product.
• Frequency within set limits
This will depend on the nominal frequency congured.
Loss of Neutral
When used on three phase + neutral applications the loss of neutral will be detected for unbalanced loads with
the load connected to the supply. Detection is done when the load is on.
Loss of the main or alternative supply.
Loss of supply depends on the nominal voltage and frequency congured together with the hysteresis set in the
product. The supply will be considered as failed after the failure timer FT has elapsed.
Return of supply depends on the phase rotation, nominal voltage and frequency congured together with the
hysteresis set. The supply will be considered as returned after the return timer RT on the ATS controller has
elapsed.
Measurement accuracy: Frequency: 0.1% - Voltage: 1%
Voltage Sensing
Source II
1Ph / 3Ph
(0 - 332 /
575VAC)
Voltage Sensing
Source I
1Ph / 3Ph
(0 - 332 / 575VAC)
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
To D10
To D20
64B 63B
64B 63B
417 416 415 414 413
207 208 209 210
417 416 415 414 413
207 208 209 210
7172 74
7172 74
ATyS t
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS p
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS g
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
To D10
To D20
64B 63B
64B 63B
417 416 415 414 413
207 208 209 210
417 416 415 414 413
207 208 209 210
7172 74
7172 74
ATyS t
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS p
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
See instruction sheet
ATS CONTROLLER
ATyS g
7/8 - 103
5/6 - 104
3/4 - 105
1/2 - 106
1/2 - 203
3/4 - 204
5/6 - 205
7/8 - 206