Troubleshooting and Maintenance
9.1 Troubleshooting
Once the inverter fails, the fault information is displayed on the App interface. If the inverter
is equipped with an LCD screen, the fault information can be viewed on it.
The fault codes and troubleshooting methods of all PV inverters are detailed in the table be-
low, and only some of the faults may occur to the model you purchased. When a fault occurs,
you can check the fault information according to the fault code on the mobile app.
Fault Code Fault Name Corrective Measures
2, 3, 14, 15
Grid Overvoltage
Generally, the inverter will be reconnected to the
grid after the grid returns to normal. If the fault oc-
curs repeatedly:
1. Measure the actual grid voltage, and contact
the local electric power company for solutions if
the grid voltage is higher than the set value.
2. Check whether the protection parameters are
appropriately set via the App or the LCD. Modify
the overvoltage protection values with the con-
sent of the local electric power operator.
3. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.
4, 5
Grid Undervoltage
Generally, the inverter will be reconnected to the
grid after the grid returns to normal. If the fault oc-
curs repeatedly:
1. Measure the actual grid voltage, and contact
the local electric power company for solutions if
the grid voltage is lower than the set value.
2. Check whether the protection parameters are
appropriately set via the App or the LCD.
3. Check whether the AC cable is firmly in place.
4. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG10RS and is the answer not in the manual?

Sungrow SG10RS Specifications

General IconGeneral
Rated Power10 kW
Max. DC Voltage1100 V
Number of MPPTs2
Max. Efficiency98.6%
Protection RatingIP65
Start Voltage180 V
Rated AC Output Power10 kW
Max. AC Output Power11 kW
Rated Output Voltage230 V
Operating Temperature Range-25°C to 60°C
TopologyTransformerless
Cooling MethodNatural Convection
Maximum Power Output11 kW
Maximum Input Current25 A
MPPT Voltage Range160-1000 V
Max. DC Input Power15 kW
AC Voltage Range180-280 V
Humidity Range0-100%
CommunicationRS485

Related product manuals