To Configure Quick Start
1. Touch , then > Options Setup > Quick Start Settings.
The QUICK START SETTINGS panel displays.
2. Refer to below, and select the configuration options for your system.
NOTE: Depending on the type of thermal management unit, included components, and control settings of your
system, all of the options listed may not be available on your iCOM display.
Quick Start Options
DX Quick Start
Enables/disables DX quick start.
DX Quick Start Initial Call for Cooling
Compressor output percentage (call for cooling) during quick start operation (0–100%).
DX Quick Start with Econophase
Enables/disable Econophase operation during quick start. When enabled on DSE thermal management units, note the
following:
If unit was operating in pump mode at the time of power loss, unit restarts in pump mode.
If unit was operating in mixed mode at the time of power loss, unit restarts in mixed mode.
If unit was operating in compressor mode at the time of power loss, unit restarts in compressor mode.
Fan Quick Start
Enables/disables fan quick start.
Pump Start Call For Cooling
Output percentage of PRE pump quick start operation (50–100%).
Quick Start Delay
Delay before quick start activates after power is restored (0to180 sec).
NOTE: When using DX quick start, you must configure a minimum of 40seconds to allow time for global condenser
communication to establish before the compressors are powered on.
Vertiv™ | Liebert® iCOM™Installer/User Guide